Specifications:
1. Maximum range trundown 100: 1
2. Backlight LCD display for the dark environment
3. Separate electronics and connection compartments
4. Excellent stability
5. Three-key adjustment
Application conditions:
* Humidity: 5...98%
* Ambient and operation: -40-85ºC (without display), -20-70ºC (with display)
* Storage: -40-85 ºC
* Ingress protection: IP 65
* Electromagnetic compatibility(EMC): Interference immunity and interference emission according to GB/T17626.2-1998), compliance with IEC 61000-4-3: 1995.
Supply voltage: | 10.5...45 VDC | |||
Output | 4...20 mA +HART protocol digital communication | |||
3-wire-system (optional): 1...5V | ||||
Signal range: | 3.8mA...22.8mA | |||
Accuracy | 3S: 0.1% accuracy for range trundown 5: 1 (0.1+0.01XURL/Span) between 1/5 and 1/50 of measuring | |||
4S...7S: 0.075% accuracy for range trundown 10: 1 (0.075+0.00751XURL/Span) between 1/10 and 1/100 of measuring | ||||
8S: 0.2% accuracy for range trundown 10: 1 (0.2+0.01XURL/Span) between 1/10 and 1/100 of measuring | ||||
Static pressure effect: | Zero error: 0.1%/7Mpa Span error: 0.2%/7Mpa | |||
Power supply effect: | Negligible | |||
Vibration effect: | < 0.01% of URL /g when tested 200Hz in any axis relative | |||
Installation position effect: | Zero shift which can be calibrated out, no span effect | |||
Thermal effect: | 0.45%/55 & ordm; C | |||
Static pressure: | 30bar...130bar | |||
Stability: | 0.1% of URL/1 year | |||
Switch on delay: | 5s | |||
Cycle time/Updater time: | 0.25s | |||
Damping: 0 to 100s, step: | 0.1s | |||
Rise time: | 200 ms (without consideration of electronic damping) | |||
Self stability configuration: | 0 to 2% | |||
Filter configured: | 0 to 160 uA | |||
Insulation resistance: | > 250MΩ | |||
Short-Circuit protection: | Permanent | |||
Reverse polarity protection: | No damage, and no function | |||
Overvoltage protection: | 500 V | |||
Vibration effect: | < 0.01% of URL /g, when tested 200Hz in any axis relative |